Each SidewinderTM assembly must be installed according to NFPA 13 standards and local government requirements, standards and codes.
Installation tools required:
Phillips Screwdriver
Pipe Wrench
Connect the nipple to the branch line using the wide, NPT threads of the nipple. Apply a nonhardening pipe joint compound or Teflon tape to the NPT male threads of the nipple. Tighten firmly with pipe wrench for leak proof connection.
Connect the sprinkler head to the reducer. Apply a nonhardening pipe joint compound or Teflon tape to the male threads of the sprinkler head and tighten according to the sprinkler head manufacturer’s instructions.
Connect the sprinkler hose nut to the nipple. Do not use joint compound or Teflon tape on the fine threads of the nipple. The nut on the end of the flexible hose contains a gasket which provides the watertight connection. Tighten the nut onto the nipple. Tightening torque: 14.7 ft-lbs (20 Nm).
Bend the flexible hose by hand to the desired route for sprinkler head placement. Minimum bend radius: 6″. Maximum number of bends: three. Do not bend within 2.5″ of either end fitting.
The ceiling grid clamps are already attached to the support bar. Attach the ceiling grid clamps to the rails of the suspended ceiling. Then use the reducer clamp and attach the reducer to the support bar. Tightening torque for all clamp screws: 4.1 ft-lbs (5.5 Nm).
Test the sprinkler system for leaks pursuant to applicable codes.